Search Catalog
      GO   
 All Categories    Kaeser Blower Purge Dryers - KBD Series
All Categories > Aftercoolers and Dryers > Desiccant Dryers > Kaeser Blower Purge Dryers - KBD Series > Item # KBD 500  

Item # KBD 500


    Download PDF Download PDF   
    border="0" Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

Flow Capacities Maximum inlet flow capacities at various pressures:
To determine a dryer's inlet flow capacity at inlet pressures other than 100 psig, multiply the dryer's rated inlet flow (found in Table 1) by the multiplier from Table 2 that corresponds to the system pressure at the dryer inlet.
KAD Dew Point Options Meet ISO 8573.1 Air Quality Standards (Table 3)
Models KAD and KAD PS allow the user to select outlet pressure dew points corresponding to the four different ISO 8573.1 air quality classes.
KAD E models are preset to deliver the commonly used ISO 8573.1 Class 2 outlet pressure dew point.
Outlet flow capacities:
For dryers operating at less than maximum flow and using the Purge Economizer feature and/or operating at pressures other than 100 psig, contact factory for correct purge flow. -

Average Heater kW (fixed cycle) = (kW required to produce 280°F temperature rise) x (235 min. max heat time) / (240 min drying time)
Average Blower kW (fixed cycle) = (Blower kW) x (235 min. max heat time) / (240 min dryer time)
Average Dryer kW (fixed cycle) = (Average Heater kW) + (Average Blower kW)
Actual kW is normally much lower and proportional with the average annual water load presented to the dryer.






Specifications

Manufacturer

Product Family

Desiccant Dryers

Series

KBD

Inlet Flow at 100 psig 100ºF

500 scfm

Width

53 in.

Depth

52 in.

Height

105 in.

Connection Size (Inlet/Outlet)

2 in.

Connection Type (Inlet/Outlet)

NPT

Weight

1776 lbs

Nom. Heater

10 kW

Avg. Heater

6.4 kW

Pre-Filter (KOR Series)

625

High Temp After-Filter (HTA Series)

600

Desiccant Per Tower

354

Blower Flow Rate

94 scfm

Nom. Blower

2.5

Avg. Blower

1.6

Other Options

Dew point monitor
High humidity alarm

Insulation for heated desiccant air dryers

NEMA 4 low ambient protection packages

Parallel piped pre-filters and after-filters

Stainless steel or copper pilot and instrument air tubing and fittings


 MORE IMAGES 

·  Inlet Pressure Correction Factor


 DOWNLOADS 

Options
(PDF, 137KB)